GENERATOR SIZING FOR PUMP STARTING
|
||||
DETAILS OF LOAD
|
||||
Consider 4 Pump motors of 60
kW , 400 V, 50 Hz each is connected to a Panel fed from a Generator.
Pump motors are started using soft starters. Running conditions are ;a) All
pumps could be running one time b) Pumps could start one by one c) 3 Pumps
running and one could be starting.
|
||||
SIZING CRITERIA
|
||||
1. Running kW or kVA
should be less than the selected Generator capacity
2.Wosrt case
starting scenario: Total kVA or kW required should be within the sKVA
rating of the Generating set.( sKVA rating shall be available in the
Generator catalog) otherwise consider 1.5 times the Generator kVA rating.
|
||||
RUNNING
|
||||
Maximum running
load= 4 pumps running
|
||||
Pump rating=60kW,
efficiency=91.8%
|
||||
running
kW=60/0.918=65.35 kW
|
||||
running
kVA=65.35/0.8=81.68 kVA
|
||||
Total kW( 4 pumps
running)
|
261.4
|
kW
|
||
Running pF=0.8 (
lowest valve from pump catalog)
|
||||
Total kVA required
while running= 245 kVA
|
326.75
|
kVA
|
||
STARTING
|
||||
Worst case could be
3 pumps running and 4th starting
|
||||
1) 3 Pumps running
kVA= 81.68 * 3
|
245.04
|
kVA
|
||
2) 4th Pump starting
kVA
|
||||
Full load current of
One pump
|
107
|
A
|
||
Starting current
with Soft starter=2.5 FLC
|
267.5
|
A
|
||
Starting kVA of One
pump
|
185.324
|
kVA
|
||
Total starting kVA =
3 pumps running kVA + One pump Starting kVA=245+185.324
|
430.364
|
kVA
|
||
Generator selection:
|
||||
Running kVA
required
|
326.75
|
kVA
|
||
Starting kVA
required
|
430
|
kVA
|
||
Generator
required ,considering 80% loading of Generator
|
408.4375
|
|||
Nearest available
size
|
400
|
kVA
|
||
400 KVA PRIME RATED GENERATOR
SUITS THE REQUIREMENTS
|
||||
………… A blog to give technical info to budding electrical design engineers in the building services industry...……
9/03/2015
GENERATOR SIZING FOR PUMP STARTING
9/02/2015
Cable Sizing Calculations
CABLE SIZING CALCULATIONS
( This article is draft stage and is under modification..........)
In electrical system design, cable sizing is one of the major activity.
Simplified Procedure for cable sizing;
• Determine the design current
• Decide the Protective device rating
• Decide the installation method of cable
• Identify the de-rating factors
• Find the Calculated current rating of required cable
• Select the cable
• Check the voltage drop
• Check the short-circuit capacity
STEP-1 : CALCULATE THE DESIGN CURRENT
Use # phase power formula to calculate the design current
Let's assume P=50 kW, v=415 V, and pf=0.8
• Where P is 3 phase load in kW and V is the Line to Line voltage.
• pf is the power factor of the load which may be taken as 0.8 , if otherwise not known.
we would get Ib= 50/ (1.732 * 0.8 * 0.415 ) = 86.95 Ampere
If it is a motor load, we have to divide by efficiency so as to get the input current drawn.
STEP-2 : SELECT THE PROTECTIVE DEVICE RATING
Protective device ( MCB/MCCB circuit breaker) is selected to protect the cable against damage from thermal overload.
Protective device must be selected such that Nominal rating of the device is more than the design current, i.e
Subscribe to:
Posts (Atom)