Here I am giving few thumb rules for electrical calculations:
kVA to Current
Current= 1.443 x kVA ( 3 phase 400 Volts)
Current= 1.39 x kVA ( 3 phase 415 Volts)
Eg:- 1000 kVA Transformer’s Full load current on LT side
1.443 x 1000= 1443 Amperes ( 3 phase 400 Volts)
1.39 x 1000 = 1390 Amperes ( 3 phase 415 Volts)
kW to Current ( power factor assumed as 0.8)
Current= 1.8 x kW (3 phase 400 Volts)
Current= 1.74 x kW (3 phase 415 Volts)
Power in 3 Phase circuit
kW= \/ 3 x V x I x cos φ
V= Line voltage ( 400 or 415 Volts)
I = Per phase current (Ampere)
Power factor correction Capacitor
Capacitor size= kW * (tan θ 2 -
tan θ1) (kVAR)
cos θ1 = system power factor(say 0.8)
cos θ2 = Desired power factor( say 0.9)
Capacitor current
Ic = kVAr / \/ 3 x V ( V= 0.400 or 0.415 kV )
Breaker and Cable size for capacitor = 1.35 x Capacitor current (Minimum)